116 Installation
director onto the exhaust hood of the outdoor unit to facilitate heat dissipation. See the figure below. The
height of the air director is HD (namely H-h). Please make the air director on site.
5) For limited space installation
The dimensions should meet the request according to the marks, otherwise, a mechanic exhaust device
must be added.
Note: 300mm=11-13/16in., 1000mm=39-3/8in.
6) Set the snow-proof facility
In snowy areas, facilities should be installed to prevent snow. (See the figure below) (defective facilities
may cause malfunction.) Please lift the bracket higher and install snow shed at the air inlet and air outlet.
>1m
100-500mm
Front Front
>1m
>1m
h
h-H
H
A
B
C
D
>45°
>1000mm
>300mm
Airflow deflector
Front view
B
A
B
A
C
D
Side view
B
A
Front view
Front view
Snow shed for air outle
Snow shed for air inlet