Set Temperature Compensation:
With the display o󰀨, press and hold the FAN button for 5 seconds. The display will then show O (default) or current
compensation setting. Use TEMP+/- buttons to adjust the compensation. Compensation can be set in 1 ° incre-
ments +/- 8°F (0.5°C increments up to +/-4°C).
Temperature compensation changes the ambient temperature reading. If the system is sensing the ambient tem-
perature at 22°C and the compensation is set to -2° then the system will use 20°C in its operation to heat or cool.
Forced Defrost:
Set to Heating mode, high fan, and 86°F (30°C), or highest temperature if ECO is on. Press TEMP+ 6 times within
5 seconds. Three tones will conrm that the unit is in forced defrost
mode.
Forced Cooling:
Set mode to Cool. Tap ON/OFF. Tap any button, except ON/OFF, to light up the display. Press and hold ON/OFF
for 5 seconds. LL will display and the control will beep twice. To exit, turn o󰀨 control and turn it on again.
Forced Heating:
Set mode to Heat. Tap ON/OFF. Tap any button, except ON/OFF, to light up the display. Press and hold ON/OFF
for 5 seconds. HH will display and the control will beep twice. To exit, turn o󰀨 control and turn it on again.
Temperature Compensation
10