SPT Sensors
   
 
 
 
Carrier Sensors    CARRIER CORPORATION ©2021  
Installation Guide    All rights reserved 
  21 
 
WARMER and COOLER 
buttons 
To raise or lower the zone's setpoint: 
1  Press either button to display the current average setpoint (the average 
between the heating and cooling setpoints). 
2  Press either button again to raise or lower the setpoint. You can adjust the 
setpoint by no more than the amount defined in the Max Adjust field*. 
NOTE Pressing either button overrides an unoccupied schedule and sets the zone 
to occupied for the amount of time defined in the Each pulse field*. 
Press to cycle through the: 
•  zone temperature 
•  outside air temperature, if enabled in the control program 
•  override time, in minutes 
•  heating setpoint 
•  cooling setpoint 
  
SPT Pro Plus 
The SPT Pro Plus has all the features of the SPT Pro plus the additional functionality described below. 
The Timed Local Override section of the microblock dialog box determines if 
pressing the MANUAL ON button sets the zone to occupied for a set amount of 
time in the same manner as the SPT Pro or sets the zone to continuously occupied. 
This button cycles through the same information as the SPT Pro. 
 
 
 
To change sensor properties 
You can use the i-Vu® application or Field Assistant, if included with your system, to change sensor properties 
such as the override time or maximum setpoint adjustment. Go to Properties page > I/O Points tab > and click on 
your applicable sensor point, i.e. Space Temp, SPT Temp Sensor, Zone Temp Sensor > Details tab of microblock 
popup.   
Field Assistant runs on a laptop that you connect to an SPT sensor's Local Access port. 
 
 
 
 
 
 
 