Alternate space temperature sensor
Carrier Sensors CARRIER CORPORATION ©2021
Installation Guide All rights reserved
26
Wiring specifications
If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Mounting location
Mount the sensor:
• In an area representing the average temperature in the space
• On an interior wall
• Approximately 5 feet (1.5 meters) from the floor, or as required by local code
• At least 4 feet (1.2 meters) from any corner
• At least 2 feet (.6 meter) from an open doorway
Do not mount the sensor:
• In drafty locations such as near air conditioning or heating ducts, or near open windows
• Over heat sources such as baseboard heaters, radiators, directly above wall-mounted lighting dimmers, or in
direct sunlight
NOTE The sensor mounting plate accommodates the NEMA standard 2x4 in. standard single gang electrical box.
However, the sensor can be mounted directly on the wall surface if local codes permit.