44 – Monitoring – User manual – v1.2
T2S Configuration Parameters
;40; ;Number of DC input groups; ;1;
¾ Number of DC groups
¾ Allows to feed several groups of inverters from several sets of batteries physically separated
;41; ;Number of AC input groups; ;1;
¾ Number of AC groups
¾ Allows to feed several groups of inverters from different Mains physically separated (i.e : Main network and
Diesel generator)
¾ This parameter is also use for 3 phases system which requires a CANDIS to display correct values
;43; ;Partial load on DC; ;25; ; ;
¾ Sets the percentage of the load to be on DC and AC, when digital input 2 is active AND a specific text in field 902
(refer to param 902) .
¾ This feature is active when the digital input 2 is activated. During this time the TSI inverter shares the input source for
example 25% from DC and 75% from AC. This Parameter can be set from 0 to 100%.
¾ By default, the value is 100% on AC
¾ In order to activate this option, a specific text must be written at the ID 902 text field see param 902.
;44; ;Disable AC Group 4 Alarm (No: 0, Yes: 1) ; ;0; ; ;
¾ Allows to inhibit the alarm monitoring when no AC In is present on AC GR 4 input (since T2S version 3.30)
¾ 0 : monitor the AC GR 4 if the configuration include 4 group
¾ 1 : doesn’t monitor the AC GR 4. Typically for clock system.
7.2 Inverter Parameters (ID 51 – 550)
;60; ;Input Source (AC : 0, DC : 100) ; ;0; ;%;
¾ Defines the priority source
¾ 0 Feeding from ACin has priority (converter AC/AC - EPC mode) default value
¾ 100 Feeding from DC has priority (converter DC/AC - On Line mode)
¾ Since software version 180, it is possible to set the share between DC and AC from 0 to 100% by steps of 1%.
¾ When parameter 43 is activated (through external signal on DIGITAL INPUT 2 with specific text to be used) the
parameter 60 takes the value recorded in parameter 43.
¾ When there is no external signal on DIGITAL INPUT 2 or when text is different than the specific requested text, the
share between DC and AC takes the value of parameter 60.