52 – Monitoring – User manual – v1.2
T2S Configuration Parameters
;373; ;AC : Fac_in High Stop ; ;53.0; ;Hz;
¾ Frequency where a higher value leads the inverters outlet to stop to synchronize with ACin
Caution: WHEN PARAMETER 75 IS SET ON 60Hz, 370 to 373 must be adapted (add 10Hz)
7.3.2 Parameters for AC groups
;380; ;AC 1 : Vac_in Low Start ; ;191.5; ;V;
¾ ACin Voltage where a higher value leads the ACin to start
;381; ;AC 1 : Vac_in Low Transfer ; ;181.5; ;V;
¾ ACin Voltage where a lower value leads to the transfer of the load from the ACin to DCin
;382; ;AC 1 : Vac_in Low Stop ; ;181.5; ;V;
¾ ACin Voltage where a lower value leads the ACin converter to stops
¾ It is possible to step down to 150 Vac. In this case, the AC/DC converter will run at a lower power. The converter DC/DC
supply the rest (ONLY if DC is available, if not, there is a derating)
;383; ;AC 1 : Vac_in High Start ; ;258.5; ;V;
¾ ACin Voltage where a lower value leads the ACin converter re-start
;384; ;AC 1 : Vac_in High Transfer ; ;268.5; ;V;
¾ ACin Voltage where a higher value leads to the transfer the load of the charge from the ACin converter to the DCin
converter
;385; ;AC 1 : Vac_in High Stop ; ;268.5; ;V;
¾ ACin Voltage where a higher value leads to stop the ACin converter
;386; ;AC 1 : Stop Power (1 : no power) ; ;0; ;;
¾ Use ACin for synchronization but could never take power from AC IN (sensor). Fuel cell