53 – Monitoring – User manual – v1.2
T2S Configuration Parameters
;390; ;AC 2 : Vac_in Low Start ; ;191.5; ;V;
;391; ;AC 2 : Vac_in Low Transfer ; ;181.5; ;V;
;392; ;AC 2 : Vac_in Low Stop ; ;181.5; ;V;
;393; ;AC 2 : Vac_in High Start ; ;258.5; ;V;
;394; ;AC 2 : Vac_in High Transfer ; ;268.5; ;V;
;395; ;AC 2 : Vac_in High Stop ; ;268.5; ;V;
;396; ;AC 1 : Stop Power (1 : no power) ; ;0; ;;
¾ The same as AC Group 1
;400; ;AC 3 : Vac_in Low Start ; ;191.5; ;V;
;401; ;AC 3 : Vac_in Low Transfer ; ;181.5; ;V;
;402; ;AC 3 : Vac_in Low Stop ; ;181.5; ;V;
;403; ;AC 3 : Vac_in High Start ; ;258.5; ;V;
;404; ;AC 3 : Vac_in High Transfer ; ;268.5; ;V;
;405; ;AC 3 : Vac_in High Stop ; ;268.5; ;V;
;406; ;AC 1 : Stop Power (1 : no power) ; ;0; ;;
¾ The same as AC Group 1
;410; ;AC 4 : Vac_in Low Start ; ;191.5; ;V;
;411; ;AC 4 : Vac_in Low Transfer ; ;181.5; ;V;
;412; ;AC 4 : Vac_in Low Stop ; ;181.5; ;V;
;413; ;AC 4 : Vac_in High Start ; ;258.5; ;V;
;414; ;AC 4 : Vac_in High Transfer ; ;268.5; ;V;
;415; ;AC 4 : Vac_in High Stop ; ;268.5; ;V;
;416; ;AC 1 : Stop Power (1 : no power) ; ;0; ;;
¾ The same as AC Group 1