EasyManua.ls Logo

Chigo CCB-12HR1 - Page 57

Chigo CCB-12HR1
177 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit
54
GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indo
or
unit
Dimensi
on
Bod
y(m
m)
1189×260
×643
1189×260
×643
1425×260×6
43
1425×260×6
43
1425×260×
643
1425×260×
643
(W*H*D
)
Packing
Bod
y(m
m)
1255×325
×720
1255×325
×720
1490×325×7
20
1490×325×7
20
1490×325×
720
1490×325×
720
(W*H*D
)
Net/Gro
ss
weight
Bod
y(Kg
)
33/37 33/37 44/48 44/48 44/48 44/48
Max
pres
sure
MPa 4 4 4 4 4.5 4.5
Refrigerant type
R410A
R410A
R410A
R410A
R410A
R410A
Refri
gera
nt
pipin
g
Liquid
side/Ga
s side
mm
Φ9.52/Φ15
.88
Φ9.52/Φ15
.88
Φ9.52/Φ19.0
5
Φ9.52/Φ19.0
5
Φ9.52/Φ19.
05
Φ9.52/Φ19.
05
Drainage pipe
mm
DN25
DN25
DN25
DN25
DN25
DN25
Controller Standard for wired controller(remote controller for option)
Operation temp
°C
16
32
16
32
16
32
16
32
16
32
16
32
Ambient temp
°C
-7
50
-7
50
-7
50
-7
50
-7
50
-7
50
Application
area
m
2
28-50 28-50 40-70 40-70 55~95 55~95
Stuffing
Quantity(20'/40'
/40'HQ)
set
75/165/18
9
75/165/18
9
75/165/168 75/165/168 75/165/168 75/165/168
Notes:
1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 5m(horizontal)
2.Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 5m(horizontal)
3.Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.
Model CTB-60HR1 CTB-60CR1 CTH-48HR1 CTH-60HR1
Indoor power supply V/Ph/Hz 220~240V/1Ph/50Hz 220~240V/1Ph/50Hz
220~240V/1Ph/50
Hz
220~240V/1Ph/50
Hz
Cooling
Capacity
Btu/h 60000 60000 48000 60000
KW
16
16
14
16
Input
W
340
340
500
500
Rated current A 1.6 1.6 2.3 2.3
EER W/W 2.65 2.65 2.55 2.58
Heating
Capacity
Btu/h 60000 60000 52500 60000
KW 16 16 15.2 16
Input
W
340
340
500
500
Rated current A 1.6 1.6 2.3 2.3
COP W/W 2.61 2.61 2.71 2.54

Related product manuals