EasyManua.ls Logo

Chigo CCB-18HR1 - Page 21

Chigo CCB-18HR1
166 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R410A50Hz Universal Outdoor Series Technical Manual 4 -way Cassette Indoor Unit
18
GD Chigo Heating & Ventilation Equipment Co., Ltd.
6.5 CCA-48HR1
MODEL
CCA-48HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
28ºC
35ºC
43ºC
21ºC D
15ºC W
Total capacity kW
14.41
13.71
13.01
12.43
Sensitive capacity kW
10.65
10.54
10.39
10.45
Input kW.
4.14
4.48
4.7
4.83
24ºC D
17ºC W
Total capacity kW
14.83
14.12
13.43
12.58
Sensitive capacity kW
11.12
11.01
10.88
10.56
Input kW.
4.4
4.68
4.88
5.14
27ºC D
19ºC W
Total capacity kW
15.11
14.41
14
13.01
Sensitive capacity kW
11.17
11.09
10.9
10.65
Input kW.
4.48
4.73
5.00
5.24
29ºC D
19ºC W
Total capacity kW
15.24
14.54
14.26
13.15
Sensitive capacity kW
12.8
12.36
12.25
11.96
Input kW.
4.58
4.83
5.04
5.34
32ºC D
23ºC W
Total capacity kW
15.38
14.85
14.57
13.42
Sensitive capacity kW
13.07
12.9
12.82
12.48
Input kW.
4.69
4.91
5.23
5.44
6.6 CCA-48HR1
MODEL
CCA-60HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
28ºC
35ºC
43ºC
21ºC D
15ºC W
Total capacity kW
16.48
15.68
14.88
14.24
Sensitive capacity kW
12.16
12.07
11.91
11.97
Input kW.
4.75
5.14
5.37
5.54
24ºC D
17ºC W
Total capacity kW
16.96
16.16
15.36
14.40
Sensitive capacity kW
12.72
12.61
12.45
12.09
Input kW.
5.03
5.37
5.60
5.89
27ºC D
19ºC W
Total capacity kW
17.28
16.48
16.00
14.88
Sensitive capacity kW
12.79
12.69
12.48
12.21
Input kW.
5.14
5.43
5.81
6.00
29ºC D
19ºC W
Total capacity kW
17.44
16.64
16.32
15.04
Sensitive capacity kW
14.65
14.15
14.03
13.69
Input kW.
5.26
5.54
5.77
6.11
32ºC D
23ºC W
Total capacity kW
17.60
16.96
16.64
15.36
Sensitive capacity kW
14.96
14.75
14.64
14.29
Input kW.
5.37
5.60
6.00
6.23