4. Parameter Checking and Setting “MFG MODE”
NO
Name
scope/means
Range, Meaning
Default
P00
Power
-down recovery function
0:
off;1:on
0:
off;1:on
1
P01
Input Power:
Single / three phase selection
0:
Single-phase 1:Three-phase
0:
Single-phase power Three-
phase power
0
P02
Power frequency
0:
50HZ; 1:60HZ
5:
50HZ; 1:60HZ
1
P03
Heat source selection
0:
ground source; 1:air source
0;
ground source
1:
Air source
1
P04
Heating temperature control
method
0:
Method 1; 1:Method 2
0:
Method 1 : 1:Method 2
0
P05
Defrost method selection
0:
Method 1; 1:Method 2
0:
Method 1 : 1:Method 2
0
P06
FREECOOLING validation
0:
valid; 1:invalid
0:
valid; 1:invalid
1
P07
Frequency control method
0:
Method 1; 1:Method 2
0:
Method 1; 1:Method 2
0
P08
DHW validation G1
0:
valid; 1:invalid
0:
valid; 1:invalid
1
P09
Air conditioning and heating
validation
0:
valid; 1:invalid
0:
valid; 1:invalid
0
P10
Air conditioning and Cooling
validation
0:
valid; 1:invalid
0:
valid; 1:invalid
0
P11
DHW hot water temp hysteresis
2~
15℃,minus hysteresis
2~
15℃,minus hysteresis
2℃
P12
AC temp hysteresis
2~
15℃,minus hysteresis
2~
15℃,minus hysteresis
2℃
P30
fan motor Category
0=AC
fan, 1=EC fan1, 2=EC fan 2
0=AC Fan, 1=EC Fan1, 2= EC
1
P31
Maximum speed of the fan
10
-100(100 show1 00%)
1-
10(10=100%)
100
P32
Heating fan speed control
temperature difference
2~
15℃
2~
15℃
6℃
P33
Cooling Fan speed control
Temperature difference
5~
18℃
5~
18℃
12
℃
P34
Defrost method
0:
Method 1;
0:
Method 1;
0
P35
defrost starting temp
-5~5
℃
C00 Pipe sensor
-1
℃
P36
defrost interval time multiple rate
0:
Not defrost;1;2;3;4:
(
interval X 4)
0:
Not defrost;1;2;3;4
:
(
interval X 4)
1
P37
The first defrost interval
15~99
minu(1st interval after
repower on
)
15~99minute
(
1st interval after
repower on
)
35
P38
defrost exit temp
10~35
℃
C00 Pipe sensor
30
℃
P45
Allowed defrost coil temperature
-20~5
℃
Defrost method 1 Condition 2
-6
℃
NOTE: Your controller will show some parameters that are not listed here,
If they are not listed they are not applicable to the CX34
47