Figure 299: Conguration screen of transistor digital outputs (impulse mode).
The parameter selected is indicated in white.
It is possible that the device may measure energy exceeding its conguration.
Make sure the energy pulses correspond to the maximum energy level admitted
by the installation.
To program the transistor digital output, after conguring the variable code and the pulse time
(with the low period and high period parameters), the following formula provides a method for
calculating the number of output pulses according to the generated energy so that the pulses
do not accumulate.
3600 * PE / PT > MP → PE = MP * TP / 3600
Where:
MP : Maximum power of the installation in W.
PE: Pulse energy in Wh ( Energy meter factor )
TP : low period + high period, in seconds.
For example: If the installation can consume 100kW, a suitable conguration could be pulses
of 10W ( Energy meter factor) with a high and low period of 50 ms.
The following options appear in the lower area: