Table 124 (Continuation): Modbus memory map: Status of transistor digital outputs (Table 1)�
Status of transistor digital outputs
Configuration variable Valid data window
Alarm
Impulse
output
Alarm
Impulse
output
Not used - -
Status
(86)
0: No alarm,
1: Active alarm,
Alarm status
(86)
0: No alarm,
1: Pre-alarm,
2: Connection or disconnection delay,
3: Alarm,
4: Impulses.
(85)
If the latch option has been programmed in an alarm and it has been activated, the alarm will be unlocked with
this option.
(86)
For these variables only Function 0x04 is implemented: reading registers.
Table 125: Modbus memory map: Status of transistor digital outputs (Table 2)�
Transistor digital outputs: Slot1
Configuration variable
Address
Alarm
Impulse
output
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Latch kWh o Wh C670 C684 C698 C6AC C6C0 C6D4 C6E8 C6FC
Delay in the
Connection
Wh o mWh C672 C686 C69A C6AE C6C2 C6D6 C6EA C6FE
Delay in the
Disconnection
Factor
Energy meter
C673 C687 C69B C6AF C6C3 C6D7 C6EB C6FF
Alarm activation
date: Year
- C674 C688 C69C C6B0 C6C4 C6D8 C6EC C700
Alarm activation
date: Month
- C675 C689 C69D C6B1 C6C5 C6D9 C6ED C701
Alarm activation
date: Day
- C676 C68A C69E C6B2 C6C6 C6DA C6EE C702
Alarm activation
time: Hour
- C677 C68B C69F C6B3 C6C7 C6DB C6EF C703
Alarm activation
time: Minutes
- C678 C68C C6A0 C6B4 C6C8 C6DC C6F0 C704
Alarm activation
time: Seconds
- C679 C68D C6A1 C6B5 C6C9 C6DD C6F1 C705
Not used C67A C68E C6A2 C6B6 C6CA C6DE C6F2 C706
Not used C67B C68F C6A3 C6B7 C6CB C6DF C6F3 C707
Status C67C C690 C6A4 C6B8 C6CC C6E0 C6F4 C708
Alarm Status C67D C691 C6A5 C6B9 C6CD C6E1 C6F5 C709
Note: The 14 registers must be read at once (as a group), otherwise it will respond with an
error.