Figure 360: Setup menu : Analogue inputs
● When programming the scale, the conguration values are:
0... 20 mA, to select the scale from 0 to 20 mA�
4... 20 mA, to select the scale from 4 to 20 mA�
● When programming the Zero and the Full-scale value:
Zero is the value for which you have the start of the analogue input, 0 or 4 mA.
The Full-scale is the value for which you have the end of the analogue input, 20 mA.
Zero Value:
Maximum value: 32000.
Minimum value: -32000.
Full-scale:
Maximum value: 32000.
Minimum value: -32000.
● When programming the Decimal position:
Here you program the number of decimals that the digital input will have.
Maximum value: 5.
Minimum value: 0.
● When programming the analogue input name and the units:
Here you enter the name for recognising the analogue input (maximum of 8 characters) and
the units it will have.
299