7�6�4�- MODBUS COMMUNICATIONS
Table 152:Modbus memory map: LonWorks communications module
Conguration of the LonWorks parameters
Configuration variable Address Valid data margin Default value
Flag Service Pin
(88)
E678
0 - 1 ( Function 0x10)
1 (Function 0x04)
-
Neuron ID
(89)
E67A - E67C Decimal value -
(88)
The following functions are implemented for this variable:
Function 0x04: reading registers.
Function 0x10: Writing multiple registers.
(89)
For this variable Function 0x04 is implemented.
7�6�5�- LIST OF LONWORKS LOGS
Note: The binary les and setup le can be downloaded from Circutor’s website.
Variable Name Variable type Unit
Current L1
nvo_Ph1Current SNVT_amp_ac (139) A 1
Code Resolution Values
02 1 0..65,534
Current L2
Name Variable type Unit
nvo_Ph2Current SNVT_amp_ac (139) A 2
Code Resolution Values
07 1 0..65,534
Current L3
Name Variable type Unit
nvo_Ph3Current SNVT_amp_ac (139) A 3
Code Resolution Values
12 1 0..65,534
Phase-Phase Voltage V12
Name Variable type Unit
nvo_Ph2PhU12 SNVT_volt_ac (138) V 12
Code Resolution Values
22 1 0..65,534
Phase-Phase Voltage V23
Name Variable type Unit
nvo_Ph2PhU23 SNVT_volt_ac (138) V 23
Code Resolution Values
23 1 0..65,534
Phase-Phase Voltage V31
Name Variable type Unit
nvo_Ph2PhU31 SNVT_volt_ac (138) V 31
Code Resolution Values
24 1 0..65,534
Phase-Neutral Voltage L1
Name Variable type Unit
nvo_Ph2NU1 SNVT_volt_ac (138) V 1
Code Resolution Values
01 1 0..65,534
Phase-Neutral Voltage L2
Name Variable type Unit
nvo_Ph2NU2 SNVT_volt_ac (138) V 2
Code Resolution Values
06 1 0..65,534
318
CVM-A1000 - CVM-A1500
Instruction Manual