EasyManua.ls Logo

Circutor CVM-A1000 - Page 351

Circutor CVM-A1000
378 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(Continuation) Current measurement circuit (CVM-A1x00-FLEX)
Installation category
Standard BOLD terminals
CAT III 600 V CAT III 300 V
Accuracy of measurements (in accordance with the IEC 61557-12 standard for PMD SD/SS)
(CVM-A1x00-ITF)
���/5A ���/1A ���/0�250A
Voltage measurement
Class 0.1 ± 1 digit
(20 ...600 V~)
Class 0.1 ± 1 digit
(20 ...600 V~)
Class 0.1 ± 1 digit
(20 ...600 V~)
Neutral voltage measurement
Class 0.5 ± 1 digit
(55 ...500 V~)
Class 0.5 ± 1 digit
(55 ...500 V~)
Class 0.5 ± 1 digit
(55 ...500 V~)
Phase current measurement
Class 0.1 ± 1 digit
(0.05 ...8A)
Class 0.1 ± 1 digit
(0.01 ...1.2 A)
Class 0.2 ± 1 digit
(0.01 ...0.3 A)
Neutral current measurement
Class 1 ± 1 digit
(0.1 ...6A)
Class 1 ± 1 digit
(0.05 ...1.2 A)
Class 1 ± 1 digit
(Calculated)
Measurement of active and apparent
power (Vn 230/110 V~)
Class 0.2 ± 2 digits Class 0.2 ± 2 digits Class 0.5 ± 2 digits
Reactive power measurement
(Vn 230/110 V~)
Class 1 ± 1 digit
(0.05 ...6 A)
Class 1 ± 1 digit
(0.01 ...1.2 A)
Class 1 ± 1 digit (0.01
...0.3 A)
Active energy measurement
(IEC 62053-22)
Class 0.2S Class 0.5S Class 0.5S
Reactive energy measurement
(IEC 62053-23)
Class 1 Class 2 Class 2
Frequency measurement Class 0.02 Class 0.02 Class 0.02
Power factor measurement Class 0.5 Class 1 Class 0.5
Voltage THD measurement Class 1 (IEC 61000-4-7)
Voltage harmonics (up to 40th order) Class 1 (IEC 61000-4-7)
Current THD measurement Class 1 (IEC 61000-4-7)
Current harmonics (up to 40th order) Class 1 (IEC 61000-4-7)
Pst Flicker 5% (0.2 ... 10Pst) (IEC 61000-4-15)
Voltage unbalance Clase A (IEC 61000-4-30)
Voltage asymmetry Clase A (IEC 61000-4-30)
Current unbalance Clase A (IEC 61000-4-30)
Current asymmetry Clase A (IEC 61000-4-30)
Accuracy of measurements (CVM-A1x00-FLEX)
(90)
Voltage measurement 0.1 ± 1 digit
Neutral voltage measurement 0.5 ± 1 digit ( 55 ...500 V~)
Current measurement 0.2 ± 1 digit
Measurement of active and apparent power (Vn 230/110 V~) 1 ± 2 digits
Reactive power measurement (Vn 230/110 V~)
2 ± 2 digits
Frequency measurement Class 0.02
Power factor measurement Class 0.5
Voltage THD measurement Class 1 (IEC 61000-4-7)
Voltage harmonics (up to 40th order) Class 1 (IEC 61000-4-7)
Pst Flicker 5% (0.2 ... 10Pst) (IEC 61000-4-15)
Voltage unbalance Class A (IEC 61000-4-30)
Voltage asymmetry Class A (IEC 61000-4-30)
(90)
The precision in the measurement does not contemplate the error of the connected probe.
351
Instruction Manual
CVM-A1000 - CVM-A1500

Table of Contents

Related product manuals