Table 13 (Cont.): Variables that can be included in the .STD le.
Variables Units
Tariff
 T1-T2-T3
Total Tariff
No. of hours of the active tariff
hours
 
Cost
COST
 
CO
2
 Emissions
kgCO
2
 
Some of the variables in the �STD le require an explanation:
PST Flicker:
The device records the value obtained during the logging period (PST Flicker). The PLT value 
will be calculated by the device.
 Harmonics:
CVM-A measures and records the average individual harmonic distortion rate (up to the 63th 
harmonic) and the voltage and current THD value (up to the 40th harmonic).Each log corre-
sponds to a block of 10 cycles, within the recording period.
 Unbalance:
The device calculates the asymmetry and unbalance coefcients of the voltages and currents 
of the three-phase system. 
Asymmetry  coefcient,  Ka:  Homopolar component  to direct component ratio  in  an unbal-
anced system.
 
 
 % =  
|
|
|
|
 100 
 
=  
1 + 
1 + 
  
 
 
=  
|
|
 100 
 
Ecuación 1: Asymmetry coefcient.
Unbalance coefcient, Kd: Reverse component to direct component ratio of an unbalanced 
system.
 % =  
|
|
|
|
 100 
 
 % =  
|
|
|
|
 100
 
 
=  
1 + 
1 + 
  
 
 
=  
|
|
 100 
 
Ecuación 2:Unbalance coefcient.
K-factor, Transformer power reduction factor:
The device calculates the K-factor according to the  IEEE C57�110. The K-factor is a factor 
that is used to calculate transformer power reduction.
 
  =   
 
=
1
 
Ecuación 3: K-factor
Where:
46
CVM-A1000 - CVM-A1500
Instruction Manual