APPENDIX A
Rack Specifications
Overview of Racks, on page 39
General Requirements for Cabinets and Racks, on page 39
Requirements Specific to Standard Open Racks, on page 40
Requirements Specific to Perforated Cabinets, on page 40
Cable Management Guidelines, on page 40
Overview of Racks
You can install the switch in the following types of cabinets and racks, assuming an external ambient air
temperature range of 0 to 104°F (0 to 40°C):
Standard perforated cabinets
Solid-walled cabinets with a roof fan tray (bottom to top cooling)
Standard open racks
If you are selecting an enclosed cabinet, we recommend one of the thermally validated types, either standard
perforated or solid-walled with a fan tray.
Note
We do not recommend that you use racks that have obstructions (such as power strips), because the obstructions
could impair access to field-replaceable units (FRUs).
Note
General Requirements for Cabinets and Racks
The cabinet or rack must also meet the following requirements:
Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to
English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see
Requirements Specific to Perforated Cabinets, on page 40.