Statement 1024Ground Conductor
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority
or an electrician if you are uncertain that suitable grounding is available.
Warning
Statement 1046Installing or Replacing the Unit
When installing or replacing the unit, the ground connection must always be made first and disconnected
last.
Warning
Before You Begin
Before you can ground the chassis, you must have a connection to the earth ground for the data center building.
Step 1
Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of the grounding
wire.
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding lug, and use a crimping tool to crimp
the lug to the wire (see Callout 2 in the following figure). Verify that the ground wire is securely attached to the grounding
lug by attempting to pull the wire out of the crimped lug.
2 M4 screws used to secure the grounding lug to the
chassis
3Chassis grounding pad1
Grounding cable, with 0.75 in. (19 mm) of insulation
stripped from one end, inserted into the grounding
lug and crimped in place
2
Cisco Nexus 93108TC-FX ACI Mode Hardware Installation Guide
21
Installing the Switch Chassis
Grounding the Chassis