Switch Power Input Requirements
The following table lists the typical amount of power that the switch consumes. It also lists the maximum
amount of power that you must provision for the switch and power supply for peak conditions.
Some power supplies have capabilities that are greater than the maximum power requirements for a switch.
To determine the power consumption characteristics for the switch, use the typical and maximum requirements
that are listed in the following table.
Note
Heat Dissipation
Requirement
Maximum Power
Consumption (AC or DC)
Typical Power
Consumption (AC or DC)
Switch
3070.928 BTUs per hour900 W404 WCisco Nexus
93360YC-FX2
Power Specifications
Power specifications include the specifications for each type of power supply module.
1200-W AC Power Supply Specifications
These specifications apply to the following 1200-W AC power supplies:
SpecificationCharacteristic
Nominal range: 100-120 VAC, 200-240 VACAC input voltage
Nominal range: 50 to 60 Hz (Range: 47-63 Hz)AC input frequency
10 A at 100-120 VAC
8 A at 200-240 VAC
Maximum AC input current
800 W at 100-120 VAC
1200 W at 200-240 VAC
Maximum output power per power supply
12 ms at 650 WMaximum hold-up time
12 VDCPower supply output voltage
12 VDCPower supply standby voltage
Climate Savers Platinum Efficiency (80Plus Platinum
certified)
Efficiency rating
RSP1Form factor
Cisco Nexus 93360YC-FX2 NX-OS Mode Switch Hardware Installation Guide