b) Pull the connector block out of the power supply.
Step 3
Strip 0.6 inches (15 mm) of insulation off the DC wires that you are using.
Step 4
Orient the connector as shown in the following figure with the orange plastic button on top.
Figure 11: Wiring a 930W -48VDC Power Supply Connector Block
-48V (-DC) cable4Wire retainer lever1
Grounding cable (8 AWG recommended)5Orange plastic button on top of the connector2
-48V Return (+DC) cable3
Step 5
Use a small screwdriver to depress the spring-loaded wire retainer lever on the lower spring-cage wire connector. Insert
your green (ground) wire into the aperture and then release the lever.
Step 6
Use a small screwdriver to depress the spring-loaded wire retainer lever on the middle spring-cage wire connector. Insert
your black (DC negative) wire into the aperture and then release the lever.
Step 7
Use a small screwdriver to depress the spring-loaded wire retainer lever on the upper spring-cage wire connector. Insert
your red (DC positive) wire into the aperture and then release the lever.
Step 8
Insert the connector block back into the power supply. Make sure that your red (DC positive) wire aligns with the power
supply label, "+ DC".
Step 9
Verify that the other ends of the cables are attached to the DC power source and ground. You are then ready to turn on
the DC power source.
Cisco Nexus 9336PQ ACI-Mode Switch Hardware Installation Guide
42
Replacing Modules
Installing a DC Power Supply