6.3Whensafetydeviceturnsonandthedryerstopsrunning
6.3.1Safetydevice(RefertoP28ElectricalCircuit)
1)
Whenacompressorbecomeshotorwhenovercurrentflows,safetydeviceturnson, and
the dryer stops running. Moreover, if refrigerant high-pressure pressure rises, a
high-pressurepressureswitchwillworkandadrierwillstop.
2)
Thecontrolcircuitfusehasclungtothismachine.
3)
Settingvaluelist
MARK MODEL PARTSLIST APPLICATIONS SETTINGVALUE
RETURN
METHOD
GX8004 1.6A at100℃
GX8006 2.1A at100℃
GX8008 5.8A at100℃
GX8011
Temperature of
he compressor
upperpart
&
Current
5.8A at100℃
GX8015 6.6A at40℃
Automatic
return
GX8022 9.0A
GX8037 12A
GX8155 14A
FR01
GX8175 22A
Manualreset
FR02 GX8015
Over load protective
devices
Compressor
current
6.6A at40℃
Automatic
return
GX8000
common
Thermostatswitch
Liquidinjection
100℃ON
90℃ OFF
GX8155
Thermalswitch
Temperature of
he compressor
upperpart
85℃ON
115℃ OFF
ST01
GX8175
Thermostatswitch
Refrigerantcircuit
105℃ON
115℃ OFF
Automatic
return
GX8015
108℃ON
130℃ OFF
GX8022
Internalthermostat
Compressor
built-in
113℃ON
135℃ OFF
ST02
GX8037 Thermalswitch
Temperature of
he compressor
upperpart
85℃ON
115℃ OFF
Automatic
return
SP02 Common
Highrangepressure
switch
Refrigerantcircuit
2.75MPaOFF
2.26MPaON
Automatic
return
FU01 Common Fuse
Electric circuit
harness
5A
Exchange
6.3.2Howtoreset
1)
Turnoffthepowersupply.Itisinthestateofresetnow.
2)
Removecausesthatstoppedthedryerabnormally.
(RefertoTroubleshootingonpg.23-24.)
3)
Resetthesafetydevice.(Referto6.3.1)
4)
Turnonthepowersupply.
CAUTION
・Besuretoturnsoffthepowersupplywhenremovecausesofproblems.
・Theproductcarried thermal typesafetydevice,youmaynotbeable to restart thedryer
eventhoughremovingthecauses.Inthiscase,turnoffthepowersupplyandwaittillthe
compressorbecomescool.(normally10to15minutes)