SM-13235-A
-24-
9.Troubleshooting
Condition Causes Measures
Powersupplydidnotturnon.
Turnonthepowersupply.
Powersupplyvoltageisabnormal. Adjustthevoltage.
Connectionofharnessisbad. Repairtheharness.
“POWER”
doesnotturnon
"POWER"lampisoff. Replace "POWER"lamp.
”START”
switchwasfailed.
Replacethe
”START”switch
Safetydeviceison. Resetthesafetydevice.
Safetydeviceisbad. Resetthesafetydevice.
Powersupplyvoltageisabnormal. Adjustthevoltage.
“RUN”lampdoesnot
t
turnon.
Remotestopterminalisopen. Theremotestopterminalisshort-circuited.
The dryer does
notstartwhen
“START”switch is
pushed.
(Manualmode)
“RUN”lampturnson.
Electromagneticswitchisbad. Replacetheelectromagneticswitch.
“REMOTESTART”switchisbad. Replace“REMOTESTART”switch.
Safetydeviceison. Resetthesafetydevice.
Safetydeviceisbad. Resetthesafetydevice.
Powersupplyvoltageisabnormal. Adjustthevoltage.
“RUN”lampdoesnot
turnon.
Remotestopterminalopens.
ConnectNCswitchtoRemotestop
termin1al.
Thedryerdoesnot
startwhen
“START”switch is
pushed.
(Remotecontrol)
“RUN”lampturnson
Electromagneticswitchisbad. Replacetheelectromagneticswitch.
Solenoidvalvefordraindischargeis
bad.
Replacethesolenoidvalvefordrain
discharge.
Excesswaterdripscomeinfrom
theairinlet.
Installfilterinfrontofthedryertoremove
waterdrips.
Thepipecomingoutofthedryeris
lowerthanthedewpoint.
Coverthepipecomingoutofthedryerwith
heatinsulationmaterial.
Thebypasscircuitbeforeand
behindthedrierisopen.
Closethebypasscircuit.
Flowtreatedbythedryeristoo
much.
Adjusttheflow(1.5×ratedflowrateorless)
Although direction of
"dew point meter"
points out the green,
water comes from a
secondaryside
.
Drainpipingistoolongortoosmall.
Replaceboresize φ7mmormoreand
length2morless,andthedischargeend
releasedtoair.
Loadover
・
Ambienttemperatureishigh.
・
Inlettemperatureishigh.
・
Inletpressureislow.
・
Treatedflowrateislarge.
Lowertheloadtothelevel.
・
Lowertheambienttemperature.
・
Lowertheinlettemperature.
・
Raisetheinlettemperature.
・
Lowerthetreatedflowrate.
Dustfilterisclogged.
Cleanthedustfilter.
Whendirtissevere,itexchangesforanew
one.
Fanmotorisbad. Replacethefanmotor.
Althoughoperation
iscarriedout
Direction of "dew point
meter" does not point
outthegreen,andwater
comesfromasecondary
side
.
Ventilationisbad.
(Supply/exhaustpartof
condenserisclosed.)
Improvetheventilation.
(Movesomething on
t
he supply/exhaust
partofthecondenser.)