SM-13235-A
>
-22-
7.2 Consumables and maintenance parts
(Note: pcs/set is use quantity per 1 set of these devices.)
●
Consumables
(
The parts which will be exchanged if the state exhausting was checked periodically and it has exhausted.
)
Inspectthefollowingparts
periodically,andexchangeitbasedonExchangejudgmentstandard.
Partsname pcs/set Inspectionfrequency Exchangejudgmentstandard※
Dustfilter 1 Weekly
Whenitdamagesanddirt.
Whenitdoesnotcomeoff.
ScreenforY-typestrainer
(onlyGX8000series)
1 Monthly Whendirtdoesnotcomeoff.
Fancontrolswitch 1 - 8,000hours(2years)
Fuse 1
Eachtime
Whenbeingcutoff.
※ Becarefulthatitisnotaguaranteevaluesincetheoperationtime(years)indicatedchangeswith
operatingconditions(ambienttemperature,installationenvironment,etc.).Yearsareastandardat
thetimeofconsideringas12hours/day(JapanElectricalManufacturer'sAssociation(JEMA))x300
daysofoperatingratios.
※ Werecommendyoutokeepafancontrolswitchandafuseasspareparts.
●
Periodic maintenance parts
(
The main parts for which exchange is needed with a use situation
)
Checkthefollowingpartsperiodicallyandexchangethembasedonstandardexchangetime.
Partsname
pcs
/set
Howtoexchange
Standardexchangetime
※
Compressor 1 × 20,000hours(6years)
Fanmotor Note(a) ○ 20,000hours(6years)
Electromagneticswitch
(Forcompressor)
Note(b) ○ 20,000hours(6years)
Electromagneticcontactor
(Forcompressor)
Note(c) ○ 20,000hours(6years)
Relay(Forcompressor) Note(d) ○ 20,000hours(6years)
Relay(Forfanmotor) Note(e) ○ 20,000hours(6years)
Electromagneticswitch(Forfanmotor) Note(f) ○ 20,000hours(6years)
Solenoidvalve (Fordraindischarge) 1 ○ 20,000hours(6years)
Mainbodyofsolenoidvalve
(Forliquidinjection)
Note(g) × 20,000hours(6years)
Coilofsolenoidvalve(Forliquidinjection) Note(g) ○ 20,000hours(6years)
※ Keepinmindthatitisnotaguaranteevaluesincetheoperationtime(years)indicatedabovechanges
withoperatingconditions(ambienttemperature,installationenvironment,etc.).Yearsareastandardat
thetimeofconsideringas12hours/day(JapanElectricalManufacturers'Association(JEMA))x300
daysofoperatingratios.
Moreover,sincetimefortherateoffailureinthecasewhereyouuseitabove
thistimetoincreaseisshown,althoughitisnotnecessarytonecessarilyexchange,thisexchangetime
is exchanged when the case where there are abnormalities at the time of check, and preventive
maintenanceareperformed
・Howtoexchange
○
:
Thosewhohavetheknowledgeandexperienceofpiping,electricity,etc.Needtoperformexchange
ofparts.
(Whentherearenottheseknowledgeandexperiences,askourcompanyoraspecialcontractor.)
×:
Beforepartexchange,refrigerantrecoveryisrequired.Moreover,sincetechnicalknowledgeisneeded
forexchangework,askourcompanyoraspecialcontractor.
Note(a): 1pc/set(GX8006,8008,8015,8022,8037)
2pcs/set(GX8004,8155,8175)
Note(b): 1pc/set(GX8022,8037,8155,8175)
Note(c): 1pc/set(GX8015)
Note(d): 1pc/set(GX8004,8006,8008,8011)
Note(e): 1pc/set(GX8004,8006,8008,8011,8015,8022,8037)
Note(f): 1pc/set(GX8115,8175)
Note(g): 1pc/set(GX8004,8006,8008,8011,8015,8022,8037)