Page 18 CI Man u al
Installer Display Settings
STEP 1I
STEP 2I
STEP 3I
STEP 5I
STEP 6I
RETURN TO
NORMAL MODE
STEP 4I
STEP 1I - Press NEXT and simultaneously for 3 seconds.
STEP 2I – Hardness: Set the amount of in uent hardness using or . This display
will not be shown if FILTER is selected in Step 2F OR if oFF or a number was
selected in Step 8S. Press NEXT to go to step 3I. Press REGEN to exit Installer
Display Settings.
STEP 3I – Service Water Hardness - If a mixing valve is installed in the valve, service hardness
needs to be set. Setting range is always less than the setting in Step 2I. This screen will not be
displayed when valve is set as a Filter, or if Auto is not selected in Step 8S.
Press NEXT to go to Step 4I. Press REGEN to return to previous step.
STEP 4I – Day Override: When volume capacity is set to oFF, sets the number of days between
regenerations. When volume capacity is set to AUTO or to a number, sets the maximum number of
days between regenerations. If value set to oFF, regeneration initiation is based solely on volume
used. If value is set as a number (allowable range from 1 to 28) a regeneration initiation will be
called for on that day even if suf cient volume of water were not used to call for a regeneration. Set
Day Override using or :
number of days between regeneration (1 to 28); or
oFF.
See Setting Options Table for more detail on setup. Press NEXT to go to step 5I. Press REGEN to
return to previous step.
STEP 5I – Next Regeneration Time (hour): Set the hour of day for regeneration using or
buttons. The default time is 2:00. This display will show “REGEN on 0 m
3
” if “on 0” is selected in
Set Regeneration Time Option in OEM Softener System Setup or OEM Filter System Setup. Press
NEXT to go to step 6I. Press REGEN to return to previous step.
STEP 6I – Next Regeneration Time (minutes): Set the minutes of day for regeneration
using or . This display will not be shown if “on 0” is selected in Set Regeneration
Time Option in OEM Softener System Setup or OEM Filter System Setup. Press
NEXT to exit Installer Display Settings. Press REGEN to return to previous
step.
To initiate a manual regeneration immediately, press and hold the REGEN button for three seconds.
The system will begin to regenerate immediately. The control valve may be stepped through the
various regeneration cycles by pressing the REGEN button.
Units
Available
PPM
FH
dH