Section 4 — System Configuration Hawk 1000
4-14 Part No. 750-366
Figure 4-13. Analog Inputs (hot water)
Analog Input I:2.3
For Steam systems Analog Input I:2.3 can be selected as None, Water Level, Remote Modulation, or Remote
Set Point. If Water Level is selected it is mandatory that the Level Master is the sensor used to measure the
water level. Remote Set Point is not available on Low Emission boilers <60ppm.
750-281
Level
Master
For Hot Water systems Analog Input I:2.3 can be selected as None, Remote Modulation, or Remote Setpoint
If Analog Input I:2.3 is used for Remote Modulation or Remote Set Point then neither Remote Modulation by
communications or Remote Setpoint by communications are available.