Hawk 1000 Section 5 — Commissioning
Part No. 750-366 5-5
5.2.1 Store Purge
The first step is to store the Purge position. A help screen is available to guide the user through storing the
Purge (and Lightoff) positions:
Figure 5-7. Purge/Lightoff help
For a valid Purge position the air actuator must be greater than 80% open. To position the actuators in setting
combustion, first press the button for the desired actuator on the Combustion Setup screen.
Figure 5-8. Combustion Setup
Next, use the <Dec> and <Inc> buttons to move the air actuator to the desired position.
Press
to
adjust
actuator