Hawk 1000 Section 5 — Commissioning
Part No. 750-366 5-11
Figure 5-20. View Actuators
The <Manipulate Actuators> button allows the actuators to travel through 0-100% of firing rate to verify all
actuators are positioning correctly at the current firing rate. To use this feature, the Burner Switch must be
OFF and firing rate must be in MANUAL mode. While manipulating the actuators, output and firing rate are
not rate limited.
5.6 Alarms and Limits
Alarms with configurable parameters and firing rate/setpoint limits can be edited from this screen.
Configurable items include the following:
5.6.1 Low O2
Select Low O2 Alarm, Shutdown, and Alarm Delay points. Low O2
Alarm only available with selection of an O2 analyzer. Shutdown only
available if selected in configuration menu.
5.6.2 Low Steam Pressure
Select Low Steam Pressure setpoint and Audible Yes/No. Alarm horn
or bell must be available for audible alarms.
Figure 5-22. Alarms and Limits - Low Steam Pressure
Figure 5-21. Alarms and Limits - Low
O2