Section 4 — System Configuration Hawk 1000
4-22 Part No. 750-366
Boiler Information
The customer name, boiler ID, and boiler serial number and can be entered. This information is displayed on
the System Information Screen. To enter this information, press the text display button beneath the
description. An alphanumeric keypad pop-up window appears.
Figure 4-22. Boiler information
Once all the information is entered, press the carriage return button. The Boiler ID and Serial Number are each
limited to 20 characters, including spaces.
If a Master Panel is being used in this system the customer name, boiler ID, and boiler serial number must be
entered again in order for this information to appear on the Master Panel HMI
Auxiliary Alarm 1-3
If the system has auxiliary alarms the text that is displayed when the alarm is triggered can be entered. To
enter this information, press the text display button beneath the description. An alphanumeric keypad pop-up
window appears.
Once all the information is entered, press the carriage return button. The auxiliary alarms are each limited to
20 characters, including spaces.
Auxiliary alarm 1 must be wired to Slot 1 Input 13
Auxiliary alarm 2 must be wired to Slot 1 Input 14
Auxiliary alarm 3 must be wired to Slot 1 Input 15
For example: If Auxiliary Alarm 1 is entered as Low Water Flow and Discrete Input I:1.13 is “On” the alarm
displayed on the HMI for Auxiliary Alarm 1 will read “Aux 1 - Low Water Flow”.