Model 4
1500 - 6000 MBTU/hr
Rev. 03-08
Section B2-31
F.
Burner Design
General
1.
The burner
shall be
integral
to the windbox.
2. All air for
combustion
shall
be supplied
by a
forced
draft blower
mounted
in the
windbox, above
the
burner,
to minimize noise
and vibration level.
3.
The blower
motor shall be an
open
drip
proof
type with a
minimum
service
factor of
1.15.
4.
The impeller
shall be an
enclosed centrifugal
fan type, properly
balanced,
and directly
connected
to the
blower
motor shaft.
5.
The combustion
air
damper
shall be
integral
to the windbox
and shall be
operated
by a
single damper
motor.
6.
The burner
shall
remain
in the low fire
position during
ignition
and until main flame has
been
established.
7. A
combustion
air
proving
switch shall be
provided
to ensure
adequate
air for
pre-purge
and combustion.
G.
Burner Design
Gas
1.
The burner
shall be the high radiant multi–port type
approved for
operation
with natural gas.
2.
The burner
shall
operate
on the (low–high–
low or full
modulation) principle
and must
return
to the low fire
position
prior to ignition.
3.
Automatic
electric ignition of the
premix gas
pilot shall be
furnished. An
electric scanner,
of the UV principle, shall
monitor the pilot,
preventing
the primary fuel
valve
from
opening
until the pilot flame has
been
established.
4.
The single combustion
air
damper
motor shall
operate
the gas
butterfly valve.
The damper
motor shall
regulate
the fire
according
to
system demand
in
response
to the firing rate
control.
H.
Burner Design
– No. 2
Oil
1.
The burner
shall be the
pressure atomizing
type
approved
for
operation
with
commercial grade
No. 2
oil.
2.
The burner
shall
operate
on the
low–high–low
principle, and
must return to the low fire
position
prior to ignition.
3.
The burner
shall
remain
in the low fire
position during
ignition
and until main flame has
been
proven.
The
ignition period
shall be monitored
with an
electric scanner,
of the
UV
principle,
to confirm the
presence
of the low fire oil flame.
4.
Automatic electric
ignition of the low fire oil
supply
shall be
provided
with a minimum 10,000 volt
transformer
and heavy
duty electrodes.
Notice
Optional insurance compliance may require
a
premix gas pilot in lieu of direct
spark
ignition.