7 - START-UP
Temperature setpoint
Set the values related to the T_SA supply air setpoint in relation to the T_OA external temperature:
(Main index \ Parameter machine \ plant config)
P0005 SetCool
P0006 SetHeat
P0010 CS_TExtCool
P0011 CS_TExtHeat
P0012 CS_GainCool (Ycool/Xcool)
P0013 CS_GainHeat (Yheat/Xheat)
Humidity setpoint
Main index \ Parameter machine \ Plant config
set the specific supply humidity setpoint in cooling mode: P0017 SetXSA
set the specific return humidity setpoint in heating mode: P0018 SetXSR
Confirm configuration
Main index \ Parameter machine \ Plant config
set P0020 ConfirmConf = Yes