9.1 Recommended periodical checks sheet
Notes/interventions recommended to Owner
* Refer to the local implemented standards.
Companies and technicians carrying out installation, maintenance/repair interventions, leaks check and recovery must be CERTIFIED as
foreseen by the local standards.
The leaks check must be carried out on a yearly basis
9 - MAINTENANCE
Checks carried out on…………………….......by……………………………...………….company…..............…………………………………………….
intervention frequency (months)
1 6 12
presence corrosion
panel fixing
fans fixing
coil cleaning
bowl cleaning + sanitisation
outflow test
air filters cleaning/inspection
air flow rate measurement
channelling: anti-vibration devices and fastenings check
power supply cable isolation and fastening check
earth cable check
electric control board cleaning
power remote controls state
clamps closure, cables isolation integrity
phases unbalancing and power supply voltage (vacuum and loaded)
absorption of the individual electric loads
compressors carter heaters test
leaks control *
cooling circuit work parameters detection
four-way valve exchange check
safety valves
*
protective equipment test: pressure switches, thermostats, flow meters, etc.
protective equipment test: setpoint, climatic compensations, power slicing, air flow rate variations
control devices test: alarms signal, thermometers, probes, pressure gauges, etc.
electrical heaters check - option
water coil check - option