When the external wire enters the interior of the unit through a waterproof cable connector, you need to separate the
strong-current cable from the weak-current cable for cabling. For details, see the diagram.
Inside the unit, wires should be fixed by using a cable tie through the overpass-shape component.
The signal cables X1/X2 and P/Q/E must be fitted with a magnetic ring, and then all cables fixed on the overpass-shaped
component by using a cable tie.
Free electrical signal port N1/N2
Cheap electrical signal port M1/M2
Connection signal ports for the hydro module and
ODU communication.
Connection for other components
1
CN15 CN17
CN20
CN21 SV3 CN22
N MSP1 N NMSP2 ALN.OY1 Y2
N N
N
X2X1
N2N1 M2M1 QP D2D1
C-PUMP
DHW-
PUMP
N.C
2 3 4 5
EE
6 7 8 9 10 11 12
{
{
{
{
{
{
{
{
{
{
{
{
Coding
1
2
3
4
5
6
Coding
7
8
9
10
11
12
Assembly unit
Connecting the wired controller
Free electrical signal
Cheap electrical signal
Outdoor commmunication bus
Hydraulic module group control interface/connecting
to the KNX gateway
Reserved
Assembly unit
Connecting the circulating water pump AC contactor
Connecting the AC contactor for controlling water
tanks and water pumps
Connecting the three-way valve
Multiple set point 1
Multiple set point 2
Alarm output 220-240V~
Wired controller wiring
X1X2
Hydro module
Wired Controller
X2
X1
CN15
Wires X1 and X2 do not have polarity requirements
Voltage
Maximum running current (A)
Wiring size (mm
2
)
18 V DC
0.1
2x0.5
Voltage
Maximum running current (A)
Wiring size (mm
2
)
12 V DC
< 0.1
2x0.5
Voltage
Maximum running current (A)
Wiring size (mm
2
)
5 V DC
< 0.1
3x0.75 shielded cable
Used for energy management and to identify free valley.
When N1 is connected to N2, the electricity is
determined to be free electricity. When M1 is connected
to M2, the electricity is determined to be cheap
electricity. When receiving cheap or free electrical signal,
the hydro module will automatically start. (For detailed
settings, refer to the User Manual.)
CN15
N2N1
M2
M1
Used to connect the hydro module and ODU communi-
cation and transfer the control signals of the the hydro
module and ODU. Please use the wire with a shield layer
and ensure that the shield layer is grounded. For
instructions on how to connect the ODU or MS, please
CN17
Q EP
To Outdoor
units comm.bus