19
Outdoors Equipment room Indoors
Space0Space1
Space2
When one hydro module is connected to multiple terminals that have different temperature requirements (such as the
floor heating device, fan coil unit, and radiator), you need to use the multiple set point function.
STATEMENT
On-site settings of the wired controller:
MENU
OPERATION PARAMETER
FOR SERVICEMAN
OK
2/2
ENTER
SCROLL
FOR SERVICEMAN
1. DHW MODE SETTING
2. HEAT MODE SETTING
4. MULTIPLE SET POINT SETTING
3. WEATHER TEMP.SETTING
5. HOLIDAY AWAY SETTING
6. SERVICE CALL
OK
1/2
ENTER
SCROLL
1. DHW MODE SETTING
√
YES
NON
√
YES
NON
DHW MODE
SCROLL
DHW MODE=YES
DHW mode is invalid.
HEAT MODE=YES
Heat mode is invalid.
Temperature settings
t_DI_HIGH TEMP.
t_DI_MAX
DISINFECT
dTtankSH
Ttank_DI
5 °C
65 °C
15 min
210 min
2. HEAT MODE SETTING
LEAVING WATER TEMP.
T_ODU_T4_FRESH_H
ROOM TEMP.
dTwoutSH
dTaSH
√
YES
NON
√
YES
NON
√ YES NON
HEAT MODE
SCROLL
0.5 h
5 °C
2 °C
04:27 27-05-2019 sun
MAIN
DHW
SET
TANK
ON ON
45
°C
45
°C
Sets the desired water
tank temperature.
Sets the desired water
outlet temperature, ranging
from 25°C to 80°C.
Water outlet temperature control
Only heating mode is available and there are multiple set points for heating mode.
FCU
5
6
9 10
11
FHL
12
8
4
radiator
1
2
3
6
7
9
ODU
Hydro module
Water flow switch
Wired controller (Accessory)
Y-shaped filter (Accessory)
Check valve (Field supply)
Safety valve (Accessory)
Water pump (Field supply
For model selection, see page 22.)
Drain valve (Field supply)
Water replenishing valve
(Field supply)
Water collector (Field supply)
Water expansion tank (Field
supply. For model selection, see
page 22.)
1
2
3
4
5
6
7
8
9
10
11
12