10
Room temperature control
In room temperature control mode, set the desired room
temperature. The hydro module will control the operating
of the hydro module according to the room temperature
collected by the wired controller. The desired room
temperature can be set manually, or through the timer
function and weather temperature curve.
Take the following steps to set room temperature
control mode: MENU > FOR SERVICEMAN > HEAT
MODE > ROOM TEMP..
Set ROOM TEMP. to YES.
Room temperature ranges from 17 C to 30 C.
Sets the mode to water outlet temperature control
and heating main interface to ROOM.
Notes:
1. The wired controller should be installed where heating
is needed.
If LEAVING WATER TEMP. is set to YES, ROOM TEMP.
is automatically set to NON. If ROOM TEMP. is set to
YES, LEAVING WATER TEMP. is automatically set to
NON.
Press
Press ▲ to choose heat mode.
04:27 27-05-2019 sun
ROOM
DHW
SET
TANK
ON ON
45
°C
°C
04:27 27-05-2019 sun
ROOM
DHW
SET
TANK
OFF ON
45
°C
°C
24
Press ▲ and ▼ to adjust desired temperature.
Press Press
04:27 27-05-2019 sun
ROOM
DHW
SET
TANK
OFF ON
45
°C
°C
25
Press ON/OFF to turn on/off heat mode.
Press ON/OFF
ON/OFF ON/OFF
Press ON/OFF
25
04:27 27-05-2019 sun
ROOM
DHW
SET
TANK
OFF ON
24 45
°C
°C
Assume that the temperature adjustment function in heat
mode or mode on/off function are locked on the wired
controller. If you adjust temperature or enable/disable a
mode, the following interface is displayed:
If you press NO, you will return to the main interface. If
you press YES, you will enter the CHILD LOCK inter-
face.
04:27 27-05-2019 sun
OK CONFIRM
NO YES
SCROLL
Heating temperature adjusting function is locked.
Do you want to unlock ?
04:27 27-05-2019 sun
OK CONFIRM
NO YES
SCROLL
Heat mode ON/OFF function is locked. Do you
want to unlock it ?
04:27 27-05-2019 sun
OK CONFIRM
HEAT TMEPERATURE ADJUSTING FUNCTION
IS LOCKED BY CENTRALIZED CONTROLLER.
If temperature adjustment function or mode on/off
function are locked on the centralized controller, the
icon on the top will be lit. If you adjust temperature or
enable/disable a mode on the wired controller, the
following interface is displayed:
In this case, the hydro module can be only unlocked on
the centralized controller.