5 - ELECTRICAL CONNECTIONS
EXAMPLE OF CONFIGURATION UNIT + DHW MODULE
Operation sequence:
With built-in keyboard:
1. UNIT CONFIGURATION menu (password required)
2. set the par 12 = 1
3. set the par 25 = 1
4. Only if the valve is provided by the customer: par 358 = see valve datasheet
With keyboard in ambient:
1. put keyboard in "system’s manager" mode
2. KEYPAD-CONFIGURATIONS menu (pag 46)
3. set the par 10 = 1
4. par 11 = 1
5. par 2 = 2
6. CONFIGURATION - SYSTEM - AUTOCONFIGURATION menu
7. Set "maxaddress = 5"
8. Wait the system components detection
9. SYSTEM-CONFIGURATION - UNIT LIST menu
10. It appears a list of the units viewed from the system