IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
Bits of this value show "1" if the bank controller receives the “GCB is closed”
message from the subordinated gen-set controller which has address
corresponding with the bit position. Bit 0 represents address 1 etc. This value
contains information about controllers with addresses 1-16.
NOTE:
The bit which corresponds to the own controller is always set to "1".
Bits of this value show "1" if the bank controller receives the “GCB is closed”
message from the subordinated gen-set controller which has address
corresponding with the bit position. Bit 0 represents address 17 etc. This value
contains information about controllers with addresses 17-32.
NOTE:
The bit which corresponds to the own controller is always set to "1".
Bits of this value show "1" if the bank controller receives the “Yellow alarm is
present in the alarmlist” message from the subordinated gen-set controller which
has address corresponding with the bit position. Bit 0 represents address 1 etc.
This value contains information about controllers with addresses 1-16.
NOTE:
The bit which corresponds to the own controller is always set to "1".
Bits of this value show "1" if the bank controller receives the “Yellow alarm is
present in the alarmlist” message from the subordinated gen-set controller which
has address corresponding with the bit position. Bit 0 represents address 17 etc.
This value contains information about controllers with addresses 17-32.
NOTE:
The bit which corresponds to the own controller is always set to "1".