IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
upload the configuration into the controller.
2. Go to InteliMonitor and change the setpoint Load ctrl PtM to ANEXT
BASELOAD.
3. Now you have to program your PLC to write requested gen-set baseload
into the Modbus register ExtValue1 (register number 40392 for IG/IS-NT-
2.4).
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object ExtValue1.
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object ExtValue1.
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object ExtValue1.