EasyManuals Logo

ComAp IG-NTC GC User Manual

ComAp IG-NTC GC
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
53
Shutdown override
If the Binary input shutdown override (Sd override) is closed, all 2
nd
level protections are disabled to allow
engine run in an emergency situation, e.g. sprinkler devices power supply.
All protections are shown in Alarmlist and recorded into History, but the controller doesn’t stop the engine
because of them. If the input is deactivated and some protections are still active or not yet reset, the
controller starts to take these protections into account and consequently stops the engine.
HINT
All 2
nd
level protections are locked out, except of these:
- Emergency stop
- Overspeed
- Underspeed (only if Fuel solenoid = GAS ENGINE)
- Binary and analog protections configured as Sd override type. In fact this protection type means
"Unoverridable shutdown", i.e. it works the same way as standard shutdown protection, however it can not
be overriden (blocked) by the Sd override input.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IG-NTC GC and is the answer not in the manual?

ComAp IG-NTC GC Specifications

General IconGeneral
BrandComAp
ModelIG-NTC GC
CategoryController
LanguageEnglish

Related product manuals