Be aware that gen-set can automatically or remotely start when following
controller terminals are disconnected !!!
• Mains voltage measuring and / or
• Binary outputs for MCB control and / or
• MCB feedback
Switch InteliGen
NT
to OFF mode and disconnect the Binary outputs Starter and Fuel
to avoid unexpected automatic start of gen-set and GCB closing.
Dangerous voltage
In no case touch the terminals for voltage and current measurement!
Always properly connect grounding terminals!
Take care when disconnecting In/Im3 terminals when the gen-set is stopped.
For safety connect parallel to controller In/Im3 terminals two anti parallel diodes
10A/100V.
In any case do not disconnect generator CT terminals when the gen-set is loaded.
Adjust set points
All setpoints are preadjusted to their typical values. But the setpoints in the “Basic
settings” settings group !!must!! be adjusted before the first startup of the gen-
set.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
CAN DESTROY THE GEN-SET !!!
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014
IGS-NT Operator Guide 01-2014.pdf