Internal Import export
ProcessControl: Load ctrl PtM = IMP/EXP
Process control: IE measurement = IM3 CT INPUT
Gen-set power is controlled to keep the import load at the level given by setpoint
Process control: Import load value.
Controller measures Import/Export value via current transformers connected to
In/Im3 terminal. The value of L3 is then multiplied by 3 to give an estimation of the
actual Imp/Exp.
InteliVision 5, InteliVision 8Operator guide, ©ComAp January 2014