Subgroup: Current Protection
Setpoint group Generator settings Related FW 1.9.0
Range [units] 100 .. 500 [%]
Default value 250 % Alternative config NO
Step 1 % of Nominal Current (page 176)
Comm object 8282 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
BOC occurs when generator current reaches this preset threshold.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Short Circuit BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.9.0
Range [units] 0,00 .. 10,00 [s]
Default value 0,04 s Alternative config YES
Step 0,01 s
Comm object 9991 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Delay for Short Circuit BOC (page 228) protection.
Short Circuit BOC Delay
6 back to List of setpoints