IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
WrnServiceT3+4). The alarm remains active until the respective counter is
readjusted back to nonzero value.
Each of the maintenance intervals can be used for different type of regular
maintenance works such as oil change, spark plug change etc.
When the particular maintenance works have been performed, readjust the
appropriate counter again to the period of next regular maintenance cycle. The
counter will then count down again.
The unused maintenance timers should be adjusted to maximal value, i.e. 65535.
Setpoint: Service time 4
This setpoint is used as maintenance interval counter #4. There are four
independent maintenance interval counters, all of them work the same way - their
values are decremented every hour while the gen-set is running and when the
zero value is reached the related alarm is issued (i.e. WrnServiceT1+2 or
WrnServiceT3+4). The alarm remains active until the respective counter is
readjusted back to nonzero value.
Each of the maintenance intervals can be used for different type of regular
maintenance works such as oil change, spark plug change etc.
When the particular maintenance works have been performed, readjust the
appropriate counter again to the period of next regular maintenance cycle. The
counter will then count down again.
The unused maintenance timers should be adjusted to maximal value, i.e. 65535.
Group: Analog protect
Setpoint: Batt >V
This setpoint adjusts the warning level for battery overvoltage alarm.
Setpoint: Batt <V
This setpoint adjusts the warning level for battery undervoltage alarm.