IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Setpoint: Batt volt del
This setpoint adjusts the delay for battery overvoltage and undervoltage alarms.
Group: Gener protect
Setpoint: OverldStrtEval
This setpoint specifies the power level relative to the nominal power, where the
thermal overload protection starts to be evaluated. See the setpoint
2PovrldStEvDel for more information about the thermal overload protection.
Setpoint: 2POvrldStEvDel
This setpoint adjusts the reaction time of the thermal overload protection if the load
level is 200% of the base level given by the setpoint OverldStrtEval.
The reaction time of the thermal overload protection is not fixed; it depends on how
much is the load above the limit (base level). The higher is the load the shorter the
reaction time will be.