PRINCIPIAL SCHEME OF A SITE IF NEUTRAL CONT = COMMON
NOTE:
As there is always a connection between the N and PE wires at the mains side the
generator neutral contactors are always open when the mains breaker is closed.
Setpoint: WatchedContr
Group
Process Control
Range [units]
0 .. 16 [min]
Related FW
3.0
Description
This setpoint is used at redundant controller to specify the address of the related
main controller in CAN-based rendundant systems. Adjust this setpoint to 0 if the
controller is not used as redundant or if wired rendundancy system is used.
Group: Basic settings
Setpoint: Nomin Power
Group
Basic Settings
Range [units]
1 .. 32000 [kW]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the gen-set nominal (rated) power, i.e. the
maximum allowed gen-set power level.
IS-NT controllers provide two independent power derating functions, which can be
used for derating of the gen-set according to an analog value (e.g. temperature).
See the setpoints Derating1 strt and Derating2 strt.
The nominal power or derated nominal power is used as the basis (100%) for gen-
set power protections, as the upper limit of the requested power in the parallel-to-

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals