is enabled, the gen-set power is limited so that mains import is always higher or
equal to the setpoint Import Load.
PRINCIPLE OF THE EXPORT LIMIT FUNCTION
This function can be used if the setpoint Load ctrl PtM is set to BASELOAD,
ANEXT BASELOAD or T BY PWR.
NOTE:
If the import value/setpoint is negative, it actually means export. This function can
be used to protect the system from unwanted export. You may set maximum
export value or you can set it possitive to keep some import even in cases that
there are abrupt load changes.
NOTE:
See the setpoint I/E-Pm meas for details about mains import measurement
methods.
Setpoint: Derating1 strt
Group
Process control
Range [units]
-32000 .. +32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the starting point of the Power derating 1
function, where the gen-set nominal power is still 100% of the setpoint Nomin
power.
See the chapter Power derating for details.
NOTE:
The setpoint actual physical dimension depends on configuration of the physical
analog input to which the logical input PowerDerating1 is assigned.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals