The actual setpoint units and range depend on setting of the Power format in
GenConfig.
Setpoint: Peak kVA Stop
If the object apparent consumption (Object P to the power of 2 + Object Q to the
power of 2) drops below this setpoint for time longer than PeakKVAS/S del, the
gen-set stops automatically (in SPtM application) or gen-set group is stopped by
InteliMains. See also the setpoint Peak kVA Start.
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
Setpoint: PeakKVAS/S del
The setpoints adjusts the delay for automatic Peak kVA start/stop function. Set 0
(OFF) to disable Peak kVA automatic start function. See also the setpoints Peak
kVA Start and Peak kVA Stop.
NOTE:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kVA is higher than Peak kVA Start).
Setpoint: Export limit
The setpoint is used to enable and disable the Export limit function. If the function