IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
102
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
Setpoint: PeakAutS/S del
Group
Process control
Range [units]
OFF, 1 .. 3200 [s]
Related FW
3.0
Force value
possible
YES
Description
The setpoints adjusts the delay for automatic Peak start/stop function. Set 0 (OFF)
to disable Peak automatic start function. See also the setpoints PeakLevelStart
and PeakLevelStop.
NOTE:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kW is higher than PeakLevelStart).
Setpoint: Peak kVA Start
Group
Process control
Range [units]
Peak kVA Stop .. 32000 [kVA]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
If the object apparent consumption (Object P to the power of 2 + Object Q to the
power of 2) exceeds this setpoint for time longer than PeakKVAS/S del, the gen-set
starts automatically (in SPtM application) or group of gen-sets is started by
InteliMains. Adjusting the PeakKVAS/S del to 0 (OFF) disables the autostart. See
also the setpoint Peak kVA Stop.

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals