IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Generator cos-phi factor.
NOTE:
The "cos-phi" factor is widely used instead of power factor for pure harmonic
waveforms, because a simplified method can be used for calculation of it's value.
However, if this simplified method is used for significantly distorted waveforms, it
may provide inaccurate results. This fact causes the controller "power factor"
value may be different from a value measured by another true-rms measurement
device if the waveform contains significant portion of higher harmonic frequencies.
Value: Load char
Character of the generator load. "L" means inductive load, "C" is capacitive and
"R" is resistive load (power factor = 1).
Value: Pwr factor L1
Generator power factor in phase L1.
Value: Load char L1
Character of the generator load in the L1 phase. "L" means inductive load, "C" is
capacitive and "R" is resistive load (power factor = 1).
Value: Pwr factor L2
Generator power factor in phase L2.
Value: Load char L2
Character of the generator load in the L2 phase. "L" means inductive load, "C" is