ï‚· Shows the text EmergMan in the engine status on the main screen.
ï‚· Stops all functions regarding the gen-set control, deactivates all outputs
related to it. The complete list of effected logical binary outputs is at the
bottom.
ï‚· Stop Fail alarm is not beeing evaluated and stop solenoid is not activated
if nonzero speed is detected.
ï‚· Voltage, current, power and other electric measurements are active.
ï‚· When the input is deactivated, the controller takes control over the gen-
set according to the situation in which the gen-set was in the moment of
deactivation. I.e. the gen-set remains running loaded if it was running and
GCB was closed in the moment the input was deactivated.
NOTE:
For successful recovery from a running state when the input is deactivated it is
recommended to use pulse-type control outputs instead of continous-type. E.g.
Stop Solenoid for fuel supply control and GCB ON coil, GCB OFF coil for breaker
control.
Logical Binary Outputs that are deactivated (directly or indirectly) when Emerg.
manual is active:
Starter
Fuel solenoid
Prestart
Cooling pump
CB close/open (GCB and MCB)
CB ON coil (GCB and MCB)
CB OFF coil (GCB and MCB)
CB UV coil (GCB and MCB)
Stop solenoid
Stop pulse
Speed up
Speed dn
AVR up
AVR dn
Ignition
Ventilation
Idle/Nominal
Prelubr pump
In synchronism
ECU PwrRelay
Ready for load
Stand-by ready
Operational
Ready
Not Ready
CranckProcedure
Starting
Idle run
Running
ForwardSynchro
ReverseSynchro
Warming
Soft load
Loaded
Soft unld
Cooling