IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
Stopping
Crancking
PeakShaveAct
Binary input: ManualLdRecon
This input is used for manual reconnection of the last disconnected part of the
load, if the load has dropped below the setpoint Ld recon level.
This input works only if automatic reconnection is disabled, i.e. the setpoint
AutoLd recon is set to DISABLED.
Binary input: FaultResButton
This input is used for an external FAULT RESET button mounted on the
switchboard. The function of the input is identical as function of the fault reset
button on the controller front panel.
The input is enabled only if the setpoint Local Button is set to position
EXTBUTTONS or BOTH.
Binary input: HornResButton
This input is used for an external HORN RESET button mounted on the
switchboard. The function of the input is identical as function of the horn reset
button on the controller front panel.
The input is enabled only if the setpoint Local Button is set to position
EXTBUTTONS or BOTH.
Binary input: StopButton
This input is used for an external STOP button mounted on the switchboard. The
function of the input is identical as function of the stop button on the controller
front panel.
The input is enabled only if the setpoint Local Button is set to position
EXTBUTTONS or BOTH.
Binary input: StartButton
This input is used for an external START button mounted on the switchboard. The
function of the input is identical as function of the start button on the controller
front panel.
The input is enabled only if the setpoint Local Button is set to position